Back

MRIO-84

  • FUNCTIONAL

    • 8 Individually configurable inputs
    • 4 individually isolated low-voltage relay outputs
    • Multiple protocol serial port including:
      - RS-232 Serial
      - RS-485 Serial
      - DMX Input
      - DMX Output
    • Tri-mode inputs support:
      - Digital In - Presence of voltage between input and ground. Supports active-high and active-low
      - Analog In - Uses voltage range as a trigger
      - Contact Closure - Uses a voltage-free switch between input and ground

    MECHANICAL

    • Six-unit wide DIN enclosure complies with DIN43880 and
      - EN60715 (35/7.5 rail)
    • Rugged aluminum enclosure
    • Rotary switch for selecting network address
    • All connections use pluggable rising clamp terminals

    ELECTRICAL

    • RJ45 connection supports 10/100Base-TX Ethernet
      - Link and data LEDs
      - Static and DHCP addressing support
    • PoE powered (IEEE 802.3af, Class 2) 7 W max draw
    • Isolated tri-mode inputs are rated for:
      - Digital - 24 VDC maximum, internal 2 MOhm pull down to 0 V (software configurable low/high threshold)
      - Analog - 0–24 VDC range configurable in software
      - Contact Closure - Voltage-free switch with internal 2.2 kOhm pull-up to 5 VDC
    • Isolated relay outputs are rated for:
      - 1 KV isolation per relay
      - 250 mA at 48 VAC/VDC (0.25 A)
      - An external power supply is required to power relay outputs
    • RS-232 or RS-485 bidirectional serial with support for free syntax ASCII, HEX or Decimal formats
      - May be used for DMX input or output of up to 512 channels
    • (ANSI E1.11-2024)
    • Wiring connections made using pluggable 0.2 in (5 mm)
    • rising clamp terminals

    THERMAL

    • Ambient temperature: 0°C to 50°C (32°F to 122°F)
    • 10%–90% relative humidity, non-condensing