Back
  •  

    ETC LED Inrush Current Ratings (Selador, Desire and Source Four LED Products) 


    Below are the inrush for ETC Selador, Desire and Source4 LED Products:

    D40

    120v:

    Recommended max number of fixtures on a typical 15A circuit breaker is 10 (Square D type QO circuit breaker).

    Max inrush current for first ½ cycle is 15A per fixture.

    1A operating current per fixture.

    Typical PF = 0.98 at maximum power draw.

    240v:

    Recommended max number of fixtures on a typical 15A circuit breaker is 10 (Square D type QO circuit breaker).

    Max inrush current for first ½ cycles is 40A per fixture.

    0.5A operating current per fixture.

    Typical PF = 0.99 at maximum power draw.

    D60

    120v:

    Recommended max number of fixtures on a typical 15A circuit breaker is 10 (Square D type QO circuit breaker).

    Max inrush current for first ½ cycles is 15A per fixture.

    1.35A operating current per fixture.

    Typical PF = 0.98 at maximum power draw.

    240v:

    Recommended max number of fixtures on a typical 15A circuit breaker is 10 (Square D type QO circuit breaker).

    Max inrush current for first ½ cycles is 40A per fixture.

    .68A operating current per fixture.

    Typical PF = 0.99 at maximum power draw.

    Source Four LED:

    120v:

    Recommended max number of fixtures on a typical 15A circuit breaker is 10 (Square D type QO circuit breaker).

    Max inrush current for first ½ cycles is 55A per fixture.

    1.11A/1.39A/1.35A operating current per fixture.  (Lustr+/Daylight/Tungsten)

    Typical PF = 0.98 at maximum power draw.

    240v:

    Recommended max number of fixtures on a typical 15A circuit breaker is 10 (Square D type QO circuit breaker).

    Max inrush current for first ½ cycles is 55A per fixture.

    0.61A/0.72A/0.72A operating current per fixture. (Lustr+/Daylight/Tungsten)

    Typical PF = 0.97 at maximum power draw.

    Selador (Lustr 11)

    120v:

    Max inrush current for first ½ cycles is 70A per fixture.

    1.05A operating current per fixture.

    Typical PF = 0.98 at maximum power draw.

    240v:

    Max inrush current for first ½ cycles is 70A per fixture.

    0.60A operating current per fixture.

    Typical PF = 0.93 at maximum power draw.

     

    PF= Power Factor